Compliance by state
Queensland smoke alarm law from 1 January 2027: what the installer has to deliver
From 1 January 2027 every Queensland house and unit, owner occupied included, must have AS 3786:2014 photoelectric smoke alarms, interconnected, in each bedroom, in hallways to bedrooms and on every storey (Fire Services Act 1990, s 147Z). Alarms must be hardwired or have a 10 year non-removable battery, and 240 volt alarms need a licensed electrician.
Last checked 25 Sep 2026 against the sources listed at the end of this page.
- Official name
- No prescribed smoke alarm certificate. The duty is in the Fire Services Act 1990, Chapter 4A Division 5A; hardwired work is covered by the electrical certificate of test
- Regulator
- Queensland Fire Department
- Who issues it
- The owner holds the duty. A licensed electrician installs and connects 240 volt alarms and issues the certificate of test for that electrical work
- When
- 1 January 2027 for every remaining dwelling; already in force for new builds, substantial renovations, sales and new or renewed leases
- Deadline
- Compliant alarms in place by 1 January 2027; replace each alarm within 10 years of manufacture or immediately on failure
- Lodgement
- Nothing is lodged for the installation itself. On a sale, the seller notifies the buyer and (unless the transfer form covers it) the commissioner
- Keep records for
- No retention period in the Fire Services Act. The electrical certificate of test copy is kept for 5 years
- Penalty
- Owner failing to install or replace compliant alarms: up to 5 penalty units ($863.50 at $172.70 from 1 July 2026). Electrician failing to give the certificate of test: up to 40 penalty units.
Homeowner? If you own and live in your Queensland home, you need interconnected photoelectric alarms in every bedroom, hallway and storey by 1 January 2027; if your current alarms are 240 volt, the new ones must be too.
What the certificate must show
- Certificate of test (hardwired work): name and address of the person the work was done for
- Certificate of test: the electrical equipment or installation tested
- Certificate of test: the day it was tested
- Certificate of test: the electrical contractor licence number
- Seller's notice to the buyer: whether smoke alarms complying with Division 5A are installed (s 148I)
Recent change
31 December 2026: s 147Y and the trigger subsections of s 147Z expire, so the full standard applies to every Queensland dwelling from 1 January 2027.
Produce it from a ServiceM8 job
- In Settings > Forms > Add Form, create a form called Smoke alarm install QLD. Build one block of questions per alarm position (Alarm 1, Alarm 2 and so on, as many as your largest typical house needs).
- For each alarm add Multiple Choice for Location (Bedroom / Hallway / Storey without bedrooms / Other), Multiple Choice for Power (240 volt hardwired / 10 year non-removable battery), a Checkbox for AS 3786:2014 marking seen, Date for Manufacture date and a Photo of the label.
- Add a Multiple Choice question, Interconnection test, with Pass / Fail, and make it mandatory: the tester sets off one alarm and confirms every other alarm sounds.
- Add a Multiple Choice question, Previous alarms were hardwired, with Yes / No, and a note telling the tech that a Yes means every replacement is hardwired.
- Map the job's client name and site address field codes and your licence number into a Word template so the report doubles as the certificate of test for the hardwired work.
- Attach the form to a Smoke alarms QLD job badge and require it before checkout, so no job closes without the per alarm record.
- Email the PDF from the job diary to the owner the same day; the seller will need it if the home is sold.
- Note the oldest manufacture date on the client record so the office can quote the next replacement before that alarm turns 10.
Why 1 January 2027 is the date that matters
Queensland phased its domestic smoke alarm law in over ten years. New builds and substantial renovations came first (from 1 January 2017), then homes being sold or leased (from 1 January 2022). The last group is everyone else, mostly owner occupiers who have not sold or rented since 2021.
The mechanism is in the Fire Services Act 1990 itself. Section 147Y, the older and looser installation rule, expires on 31 December 2026. At the same time the trigger subsections of section 147Z (building approval, sale, new tenancy) expire, which leaves section 147Z(3) applying to every domestic dwelling: the owner must install smoke alarms that meet the section. For an electrician, that means from the new year there is no longer a class of house where the old alarms are still lawful just because nothing has changed hands.
What a compliant installation looks like
Section 147Z(5) says each alarm must be powered in the way the regulation prescribes, meet the other prescribed requirements, have been manufactured less than 10 years before it is installed, operate when tested, and be interconnected to every other alarm in the dwelling. Interconnected has a plain test in section 147Z(6): if one alarm senses smoke, every other alarm sounds.
The Queensland Fire Department's guidance fills in the rest. Alarms must be photoelectric and comply with AS 3786:2014 (look for the marking on the unit). They go on each storey, in every bedroom, in hallways that connect bedrooms to the rest of the home (or between bedrooms and the rest of the storey if there is no hallway), and, on a storey with no bedrooms, in the most likely path of travel out. Interconnection can be wired, wireless or a mix of both.
Check the manufacture date printed on stock before it goes on the van. A unit that sat in a warehouse is still compliant as long as it was made less than 10 years before the day you fit it.
Hardwired stays hardwired
The power source rule is the one that most often turns a battery swap into an electrician's job. Under section 148A(3), if the alarm being replaced was hardwired to the dwelling's supply, the replacement must be hardwired too. QFD's guidance puts it the same way: homes with 240 volt alarms replace them with 240 volt photoelectric alarms, while homes with battery alarms may use 10 year non-removable battery units. New builds and major renovations need hardwired alarms.
QFD also states that 240 volt alarms connect to the electricity supply and must be connected by a licensed electrician, while non-removable battery alarms do not need one. Owners must replace any alarm within 10 years of its manufacture date, or immediately if it fails when tested (section 148A).
What to certify, and what nobody requires
There is no prescribed "smoke alarm compliance certificate" in Queensland. QFD says outright that a certificate of compliance is not a legal requirement, although some agents ask for one as part of their own process. What does apply to an electrician is the ordinary electrical rule: when your work on the installation must be tested, the Electrical Safety Regulation 2013 requires a certificate of test given as soon as practicable, showing the customer's name and address, what was tested, the test date and your contractor licence number, with a copy kept for 5 years.
So the useful document for a hardwired job is the certificate of test plus a job record of each alarm: location, type, AS 3786:2014 marking, manufacture date, power source and a pass on the interconnection test. That record answers the owner's question (am I compliant for 2027?) and protects you if a later tradie disturbs the circuit.
When the home is sold
A seller has to give the buyer written notice, on or before possession, of whether compliant smoke alarms are installed (section 148I), and must tell the commissioner within 90 days unless the property transfer information form lodged with the titles office already covers it (section 148J). Your dated job record is what the seller relies on when they tick that box, which is a good reason to email it to the owner the day you finish.
Sources
- Section 147Y (the older smoke alarm installation requirement) expires on 31 December 2026, and s 147Z(1), (2) and (7) expire on the same day, leaving the owner's duty in s 147Z(3) to install compliant smoke alarms. Maximum penalty 5 penalty units. Fire Services Act 1990 (Qld), ss 147Y and 147Z (current as at 6 December 2025), checked 25 Sep 2026.
- Each smoke alarm must be powered as prescribed by regulation, meet other prescribed requirements, have been manufactured less than 10 years before installation, operate when tested, and be interconnected to every other smoke alarm in the dwelling. Fire Services Act 1990 (Qld), s 147Z(5) and (6), checked 25 Sep 2026.
- The owner must replace a smoke alarm within 10 years after its manufacture date, or immediately if it does not operate when tested; a replacement for a hardwired alarm must be hardwired. Maximum penalty 5 penalty units. Fire Services Act 1990 (Qld), s 148A, checked 25 Sep 2026.
- The transferor must give the transferee written notice of whether compliant smoke alarms are installed on or before the date of possession, and notify the commissioner within 90 days unless a property transfer information form is lodged with the registrar of titles. Fire Services Act 1990 (Qld), ss 148I and 148J, checked 25 Sep 2026.
- All Queensland dwellings must have compliant smoke alarms by 1 January 2027: photoelectric, AS 3786-2014, interconnected, hardwired or powered by a non-removable 10 year battery, on each storey in each bedroom and hallways connecting bedrooms; 240 volt alarms must be connected by a licensed electrician; existing 240 volt alarms are replaced with 240 volt alarms. Queensland Fire Department, Frequently asked questions about smoke alarms (last updated 13 April 2026), checked 25 Sep 2026.
- There is no legal requirement for a qualification to test or clean a domestic smoke alarm, and a certificate of compliance from a smoke alarm company is not a legal requirement, though an agent may ask for one. Queensland Fire Department, Frequently asked questions about smoke alarms, checked 25 Sep 2026.
- A licensed electrical contractor must give a certificate of test as soon as practicable after testing, stating the customer name and address, what was tested, the test date and the contractor licence number, and keep a copy for 5 years. Electrical Safety Regulation 2013 (Qld), ss 26 and 227, checked 25 Sep 2026.
- The Queensland penalty unit is $172.70 from 1 July 2026. Queensland Law Society Proctor, checked 25 Sep 2026.
- Completed ServiceM8 forms convert to a PDF saved to the job diary, where they can be emailed; form answers are placed into a Word document template using Template Field Codes. ServiceM8 Help Center, checked 25 Sep 2026.