ServiceM8 fire extinguisher inspection form for AS 1851 records

This ServiceM8 Form records the AS 1851 routine service of one portable fire extinguisher: type, size, location, gauge or weight check, the service level done (six monthly, yearly or five yearly), whether the maintenance tag was punched, and defects. Completed against extinguisher assets, the Asset Register prints the site's service record in one PDF.

Last checked 25 Sep 2026 against the sources listed at the end of this page.

Free form ยท AS 1851:2012

Portable fire extinguisher routine service form for fire services

A per unit service record in the job diary and, with Asset Management, a per site extinguisher service record showing each unit's service level and result.

The form: 20 questions

SectionQuestionTypeReq.Notes
UnitExtinguisher ID or serial numberTextYes
UnitLocationTextYesSpecific enough to find it, for example Kitchen, beside rear exit.
UnitExtinguisher typeChoice
ABE dry powder / BE dry powder / CO2 / Water / Foam / Wet chemical / Other
Yes
UnitSize (kg or L)NumberYes
UnitYear of manufactureNumberYesFrom the cylinder. Drives when the longer services fall due.
ServiceService level performedChoice
Six monthly / Yearly / Five yearly (pressure test or recharge) / Replaced with new unit / Not serviced (see comments)
Yes
ChecksAccessible, visible and correctly mountedChoice
Yes / No
Yes
ChecksLocation sign presentChoice
Yes / No / Not required
Yes
ChecksGauge readingChoice
In operating range / Low / High / No gauge (CO2)
Yes
ChecksWeight (kg)NumberCO2 units are checked by weight. Skip when Gauge reading is not No gauge (CO2).
ChecksPin and tamper seal intactChoice
Yes / No, replaced / No, unit discharged
Yes
ChecksCondition defectsMultiple choice
Hose or horn cracked / Corrosion / Dent or damage / Label unreadable / Bracket loose or missing / Used or partly discharged / None
Yes
TagMaintenance tag punched for this serviceChoice
Yes / No, new tag fitted / No (see comments)
Yes
ResultResultChoice
Serviceable / Serviced and returned / Removed for workshop service / Condemned and replaced
Yes
ResultReplacement unit serialTextSkip unless Result is Condemned and replaced.
ResultPhoto of unit and tagPhotoYes
ResultCommentsText
ResultDate servicedDateYes
Sign offTechnician name and licence numberTextYes
Sign offTechnician signatureSignatureYes

Set it up in ServiceM8

  1. Turn on Asset Management and create an asset type called Fire extinguisher with fields for type, size and year of manufacture.
  2. Build the form in Settings > Forms > Add Form with the questions above, then link it to the Fire extinguisher asset type so it is suggested when a unit is scanned.
  3. Add Skip Question If conditions: Weight is skipped unless Gauge reading equals No gauge (CO2), and Replacement unit serial is skipped unless Result equals Condemned and replaced.
  4. In the asset type's template setup, choose location, type, size, service level, result and date serviced as the columns for the service report and Asset Register.
  5. Create a Form Follow Up automation with the condition Result equals Condemned and replaced, created on job completion, so the office gets one list of replacements per visit.
  6. Set a recurring six monthly job per site with the Fire extinguisher badge applied.

Stamp the service level on every unit

Extinguishers on one site are rarely on the same cycle. Most units get the routine six monthly check, but a unit bought two years after the rest reaches its longer service at a different time, and a CO2 unit is checked by weight rather than by gauge. Published summaries of AS 1851:2012 describe the six monthly routine as accessibility, pressure, physical condition and seals, weighing CO2 units, and punching the date on the metal maintenance tag, with further services at longer intervals (five yearly and beyond) that are more invasive.

So the key question on this form is Service level performed, answered for each unit. When it prints in the site record the client sees at a glance which units had only the routine check and which had a pressure test or recharge, and the next technician knows which units are due for the longer service. The tag question matters for the same reason: the punched tag on the unit and the service record should always agree.

Why extinguishers are the textbook ServiceM8 asset

ServiceM8's own help centre uses a Fire Extinguisher Inspection form as its example of completing forms against assets. Each extinguisher gets a QR label, the technician scans it, and every question shows that unit's previous answers, which makes a weight that has been dropping over two services easy to spot. Units on a site show a green tick once their form is done on the job, so the technician can see which ones are still to be found.

At the end of the job the Asset Register (Settings > Assets > Asset Register) prints every asset for the customer with the answers you choose as columns: location, type, size, service level, result and date. That PDF is the site service record. For units needing replacement, a Form Follow Up automation set to run on job completion gathers every failed extinguisher from the visit into a single Inbox message, rather than one per unit.

Who needs the record

Fire extinguishers are a prescribed fire safety installation on the Queensland occupier's statement and an essential safety measure in Victoria, so the occupier or owner will be asked to produce these records. Book the next visit as a recurring job every six months so the record never has a gap.

What this form will not do

  • ServiceM8 cannot work out which service level is due from the year of manufacture. The technician chooses it; a custom report or asset field can flag units due for the longer service.
  • Service frequencies and checks in the notes come from published summaries of AS 1851:2012, which is paywalled. Check them against your copy.
  • The form does not print or punch the physical maintenance tag, which still has to be done on the unit.
  • For a customer with several sites, use the Client Sites add-on so the technician's asset list shows only the units at the site they are standing in.

Sources

  1. Published summaries of AS 1851:2012 describe the six monthly extinguisher routine as checking accessibility, pressure, physical condition and anti tamper seal, weighing CO2 extinguishers, and punching the date on the metal maintenance tag. Complete Pumps and Fire Protection, checked 25 Sep 2026.
  2. ServiceM8's help centre gives a Fire Extinguisher Inspection form as an example of a form completed against an asset; each question shows the asset's past values and the asset is ticked green once a form is completed on the job. ServiceM8 Help Center, checked 25 Sep 2026.
  3. Settings > Assets > Asset Register produces a PDF of all assets for one customer including results of forms completed on them. ServiceM8 Help Center, checked 25 Sep 2026.
  4. A Form Follow Up automation can create its Inbox message on job completion, combining the messages for all assets on the job into one. ServiceM8 Help Center, checked 25 Sep 2026.
  5. Portable fire extinguishers are an essential safety measure in Victoria (Building Regulations 2018, Schedule 8, Part 5). Building Regulations 2018 (Vic), version 031, checked 25 Sep 2026.
  6. Fire extinguishers are one of the prescribed fire safety installations listed on the Queensland occupier's statement. Queensland Development Code MP 6.1, Schedule 2 (publication date 6 May 2014), checked 25 Sep 2026.
  7. In the ServiceM8 app the Assets view shows all assets for the client, or for the site when the Client Sites add-on is used. ServiceM8 Help Center, checked 25 Sep 2026.