FFP Guides

ServiceM8 form

Free ServiceM8 TMV service record form

This ServiceM8 Form records a routine thermostatic mixing valve service: the valve, the delivery limit that applies (45°C or 50°C under NCC 2025 Volume Three B2D5), a temperature reading at every outlet it serves, the cold isolation test, parts replaced and the next service date. It suits plumbers servicing aged care, hospitals and schools.

Last checked 25 Sep 2026 against the sources listed at the end of this page.

Free form · AS 4032.3

TMV service record form for plumbing

A per valve service record PDF in the job diary with a temperature for every outlet served, the fail safe test result, parts replaced and the next service date, signed by the tester and optionally the facility.

The form: 32 questions

SectionQuestionTypeReq.Notes
SiteFacility name and areaTextYesWing, floor or room group, as the facility names it.
SiteFacility typeChoice
Aged care residential part / Health care patient care area / Early childhood centre, children's area / School, children's area / Designated accessible facility / Other building
YesDrives the delivery limit under NCC Volume Three B2D5.
SiteMaximum delivery temperature for these outletsChoice
45 C / 50 C
Yes45 C for the first five facility types, 50 C otherwise. Check your state variation.
ValveValve ID or tag numberTextYesMatch the asset label if the valve is a ServiceM8 asset.
ValveValve locationTextYesFor example: ceiling space above bathroom 12, cupboard B2.
ValveDevice typeChoice
Thermostatic mixing valve / Thermostatically controlled tap / Tempering valve / End of line device
YesOnly a TMV or thermostatically controlled tap is allowed for the 45 C cases.
ValveMake, model and sizeTextYes
ValveSerial number or installation dateText
SupplyHot supply temperature at valve inletNumberYesDegrees C. Enter the number only. Flag readings well under 60 C to the facility.
SupplyCold supply temperature at valve inletNumberYesDegrees C.
SupplyStrainers and check valvesChoice
Cleaned, serviceable / Replaced / Not fitted
Yes
OutletsNumber of outlets testedNumberYesDrives the skip conditions on the outlet questions below.
OutletsOutlet 1 location and fixtureTextYesFor example: room 12 basin.
OutletsOutlet 1 temperatureNumberYesDegrees C after the reading stabilises.
OutletsOutlet 2 location and fixtureTextSkip if Number of outlets tested is less than 2.
OutletsOutlet 2 temperatureNumberSkip if Number of outlets tested is less than 2.
OutletsOutlet 3 location and fixtureTextSkip if less than 3. Repeat the pair for as many outlets as your largest valve serves.
OutletsOutlet 3 temperatureNumberSkip if less than 3.
OutletsOutlet 4 location and fixtureTextSkip if less than 4.
OutletsOutlet 4 temperatureNumberSkip if less than 4.
OutletsAny outlet over the maximumChoice
No / Yes
YesServiceM8 does not compare numbers for you, so the tester answers this.
Fail safe testCold supply isolation test resultChoice
Hot flow shut off / Flow reduced to safe level / Failed / Not performed
YesFollow the method in AS 4032.3 and the maker's instructions.
Fail safe testHighest temperature during isolation testNumberDegrees C.
ServiceParts replacedMultiple choice
Thermostatic element or cartridge / Seals and O rings / Strainers / Check valves / Whole valve / None
Yes
ServiceValve adjustedChoice
No adjustment needed / Adjusted and retested
Yes
ServicePhoto of valve and tagPhotoYes
ServicePhoto of highest outlet readingPhotoYesThermometer in the flow with the outlet visible.
ResultOverall resultChoice
Pass / Fail, outlets isolated / Fail, facility notified
Yes
ResultNext service dueDateYesSet by the facility's water management plan, the standard and your state rules.
ResultComments and recommendationsText (Multi-line)
Sign offPlumber licence numberTextYes
Sign offPlumber signatureSignatureYesFacility sign off uses the customer signature field in the template, not a question.

Set it up in ServiceM8

  1. In ServiceM8 go to Settings > Forms > Add Form, name it TMV service record and give it a badge name such as TMV.
  2. Add each question above in order. Choice means Multiple Choice, Multiple choice means Multiple Choice (Multi-answer). Keep question names to letters and numbers, so write 45 C, not 45°C.
  3. On each outlet 2 to 6 question, add a Skip Question If condition: Number of outlets tested, Less than, the outlet number.
  4. Click Download Sample Template to get a Word file with every Template Field Code, lay the outlets out as a table (location, temperature, limit), and add the mergefields image_customer_signature and customer_signature_date where the facility signs.
  5. Upload the template to the form, then turn on the form badge on the service job so the form appears on the tech's To Do list.
  6. If you use Asset Management, create an asset type called Thermostatic mixing valve and link this form so each valve keeps its own service history.
  7. Run it on a dummy job with a valve serving two outlets and one serving four, and check that the skipped outlets leave the PDF tidy.

Why the form starts with the building, not the valve

The number that matters on a TMV service is the delivery temperature at the outlet, and the limit depends on where the outlet is. NCC 2025 Volume Three, clause B2D5, caps heated water at sanitary fixtures at 45°C in the residential part of an aged care building, a patient care area in a health care building, the parts of an early childhood centre or school used by children, and designated accessible facilities, and at 50°C everywhere else. Clause B2D6 then says the 45°C areas must use a thermostatic mixing valve or a thermostatically controlled tap. A tempering valve is only an option for the 50°C cases.

So the first choice on this form is the facility type, and the second is the limit that follows from it. A tester who records 47°C at a hand basin in a nursing home has a fail, and the form should make that obvious on site, not when the facility manager reads the PDF a week later.

One reading per outlet, not one per valve

Plumbers who service one TMV that feeds six basins often write a single temperature on a job card. Facility managers in aged care and hospitals want to see each outlet, because a long dead leg or a failing mixer on one fixture shows up only at that fixture. The form below gives each outlet its own location and temperature question, and uses ServiceM8's Skip Question If condition so a valve serving two outlets does not force the tester through six.

ServiceM8 supports Equal to, Not equal to, Greater than, Less than, Contains and Does not contain as skip conditions. Set outlet 3 to be skipped when the number of outlets is less than 3, outlet 4 when it is less than 4, and so on.

What the cold isolation test and the storage side tell you

The field testing and maintenance procedure for TMVs is in AS 4032.3, whose full title covers field testing, maintenance or replacement of thermostatic mixing valves, tempering valves and end of line temperature control devices. The standard is sold by Standards Australia, so the form does not repeat its step by step method. It records the result of the fail safe test your procedure calls for (isolating the cold supply and confirming the hot flow shuts off or drops to a safe level), plus the temperature seen during that test.

The form also records the supply temperatures, because a TMV is only half the story. The ABCB warns that Legionella grows in water between 20°C and 45°C and that growth is reduced significantly in water stored at 60°C and above. A hot supply reading well under 60°C at the valve inlet is worth a note to the facility even when every outlet passes.

How it fits ServiceM8

Build it with the Forms add-on and link it to the valve as an asset if you use Asset Management, so each TMV keeps its own service history. Completed forms become a PDF in the job diary. If the facility wants its own staff member to sign after reading the record, put ServiceM8's customer signature field in the Word template instead of a Signature question: the app produces the PDF, the client reviews it, taps Sign Document, and the signature lands on the PDF. ServiceM8 notes this review and sign flow only works when the form is completed in the mobile app.

What this form will not do

  • ServiceM8 Forms do not check a reading against a limit, so the tester answers Any outlet over the maximum by hand.
  • The form does not reproduce the AS 4032.3 test method, which is sold by Standards Australia. Keep your procedure and the valve maker's instructions to hand.
  • Service intervals are not set here. Use the facility's water management plan, the standard and your state plumbing regulator's rules.
  • Nothing is lodged with a council or regulator by this form. Check whether your state requires a separate notice for the work.
  • Facility review and signature on the PDF works only when the form is completed in the ServiceM8 mobile app.

Sources

  1. NCC 2025 Volume Three B2D5 limits heated water delivered at the outlet of each sanitary fixture to not more than 45°C in the residential part of an aged care building, a patient care area in a health care building, parts of an early childhood centre or primary or secondary school used by children, and designated accessible facilities (with some state variations to the wording), and not more than 50°C in all other cases. Australian Building Codes Board, NCC 2025 Volume Three, B2D5, checked 25 Sep 2026.
  2. NCC 2025 Volume Three B2D6 requires a temperature control device delivering water under B2D5(a) (the 45°C cases) to be a thermostatic mixing valve or a thermostatically controlled tap; for B2D5(b) a tempering valve or temperature limited water heater is also allowed. Australian Building Codes Board, NCC 2025 Volume Three, B2D6, checked 25 Sep 2026.
  3. A state variation to NCC 2022 Volume Three B2D6 requires thermostatic mixing valve work to comply with AS 4032.3, Water Supply, Valves for the control of heated water supply temperatures, Part 3: Requirements for field testing, maintenance or replacement of thermostatic mixing valves, tempering valves and end of line temperature control devices. Australian Building Codes Board, NCC 2022 Volume Three, B2D6 state variation, checked 25 Sep 2026.
  4. Legionella grows in water at temperatures between 20°C and 45°C, and its growth is reduced significantly in water stored at 60°C and above; delivery temperature limits are separate and sit in Part B2 of NCC Volume Three. Australian Building Codes Board, checked 25 Sep 2026.
  5. ServiceM8 form questions can be skipped using IF conditions: Equal to, Not equal to, Greater than, Less than, Contains, Does not contain, and If ALL or If ANY conditions match. ServiceM8 Help Center, checked 25 Sep 2026.
  6. To have a client review a completed form before signing, the form template uses the Customer Signature field instead of a Signature question; this only works when completing forms in the ServiceM8 mobile app, and the signed PDF is saved to the job diary. ServiceM8 Help Center, checked 25 Sep 2026.
  7. ServiceM8 advises using only letters and numbers in form question names, because symbols such as / \ ( ) # & - : may cause problems when the completed form PDF is generated. ServiceM8 Help Center, checked 25 Sep 2026.